RDC2
Frequency Low
Frequency low
Electrical · Shutdown
Shutdown. TP-7092: governed frequency falls below 90 percent of the system setting for more than 10 seconds, or 1 Hz below the setting for more than 60 seconds. Active 10 seconds after engine start. The check is to reduce the load and restart, check the enclosure thermostat, then call a dealer. OnCue Plus calls the related event Generator Frequency Low.
Seen on: 14RCA, 14RCAL, 20RCA, 20RCAL, 26RCA, and 26RCAL sets with the RDC2 controller (TP-7092).
Likely causes
- Overload pulling frequency down.
- Tripped enclosure thermostat.
- Fuel or governor trouble the dealer has to separate from a simple overload.
Checks an owner can do
- Shut off large loads and restart once.
- Check the enclosure thermostat only if you can do that without opening electrical compartments.
When to call a pro
A second trip with the breaker unloaded is a dealer diagnosis.
Source
Wording follows that document. Firmware can change a threshold. If this page and the manual shipped with your unit disagree, follow the manual.
What fixed mine
No approved reports for this code yet. Send one. It stays in the review queue until it is approved.