Home / Kohler / Lo Crank Vlt

RDC2

Lo Crank Vlt

Low cranking voltage

Electrical · Warning

Warning on the residential RDC2 table. TP-7092 says battery voltage dropped below 3.5 VDC during engine cranking. The check is to charge or replace the battery. This 3.5 volt figure is the residential manual's number. Kohler's liquid-cooled TP-6905 describes low cranking voltage differently, so that threshold is not mixed in here. OnCue Plus calls the related warning Low Cranking Voltage.

Seen on: 14RCA, 14RCAL, 20RCA, 20RCAL, 26RCA, and 26RCAL sets with the RDC2 controller (TP-7092).

Likely causes

  • A battery that collapses under starter load.
  • Connections that drop the voltage the controller measures while cranking.

Checks an owner can do

  1. Have the battery tested and replace it if it will not hold a charge. Follow the battery maker's charging steps.
  2. Clean and tighten the cable ends with the generator off.

When to call a pro

If a known-good battery still falls through 3.5 volts while cranking, the cables, starter draw, or charger need a dealer.

Source

Kohler TP-7092 9/23e, Operation manual for 14/20/26RCA and RCAL residential generator sets with the RDC2 controller, fault-message table.

Wording follows that document. Firmware can change a threshold. If this page and the manual shipped with your unit disagree, follow the manual.